HomeMy WebLinkAbout889 08-26-1986ORDINANCE NO. 889
AN ORDINANCE ADOPTING THE 1985 EDITION
OF THE UNIFORM BUILDING CODE & APPENDICES,
WITH AMENDMENTS, DWELLING CONSTRUCTION UNDER
THE UNIFORM BUILDING CODE, UNIFORM CODE FOR
THE ABATEMENT OF DANGEROUS BUILDING, UNIFORM
HOUSING CODE, UNIFORM MECHANICAL CODE WITH
REVISIONS. REGULATING THE ERECTION, CONST-
RUCTION, ENLARGEMENT, ALTERATION, REPAIR,
MOVING, REMOVAL, DEMOLITION, CONVERSION,
OCCUPANCY, USE, HIEGHT, AREA AND MAINTENANCE
OF BUILDINGS AND STRUCTURES IN THE CITY OF
EULESS; REPEALING THE EXISTING BUILDING CODE
AND ALL AMENDMENTS THERETO, AND PROVIDING AN
EFFECTIVE DATE.
Whereas, it is deemed necessary to provide minimum standards to regulate
the design, construction, materials, use and occupancy, location and main-
tenance to buildings and structures, and certain equipment thereof within
the City, to protect and promote public safety, health and welfare.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF EULESS,
TEXAS:
I.
ADOPTION OF STANDARD CODES
The 1985 edition of the Uniform Building Code & appendices, with amend-
ments, Dwelling construction under the Uniform Building Code, Uniform Code
for the Abatement of Dangerous Buildings, Uniform Housing Code, Uniform
Mechanical Code & appendices, as adopted by the International Conference of
Building Officials, with revisions are hereby adopted. The Building Code of
the City of Euless, Texas is hereby revised and amended to conform to the
1985 edition of the Uniform Building Code, Dwelling construction under the
Uniform Building Code, Uniform Code for the Abatement of Dangerous Buildings,
Uniform Housing Code and Uniform Housing Code marked "Exhibit B" are incor-
porated herein by reference and have been filed in the office of the City
Secretary for permanent record and inspection.
II.
ORDINANCES REPEALED
Ordinances 28, 29, 504, 614, 715, 776, 853, and all ordinances amendatory
thereto; are expressly superseded by the terms of this ordinance.
Building permits heretofore issued under the existing ordinances shall be
valid for the time for which they were issued under the existing building code;
however, upon expiration of said date, the same shall become void.
- 1 -
y
EXHIBIT "B" TO ORDINANCE NO. 889
I.
AMENDMENTS TO THE UNIFORM BUILDING CODE
FEES, Section 304 (a) Amend to read:
(a) A building inspection fee shall be paid to the Building Official as
set forth in Table A, City of Euless, Schedule of Fees, Ordinance
No. 807.
The determination of the value or valuation shall be made by the
Building Official, if the valuation is understated on the application,
permit cost shall be denied, unless the applicant can show detailed
estimated costs to meet the approval of the Building Official.
Where work for which a permit is required by this Code is started
or proceeded with prior to obtaining said permit, the fees above
specified shall be increased fifty percent (50 %) but not to exceed
five hundred dollars ($500.00). The payment of such fee shall not
relieve any persons from fully complying with the requirements of
this code in the execution of the work nor from any other penalities
prescribed herein. -
The work will be considered started when foundation excavation is
started.
Payment of taxes, assessments, charges and other monetary obligations
due the City of Euless. No permit herein provided for shall be
issued until all ad valorem and other property taxes, assessments,
charges, and other monetary obligations due the City of Euless shall
be paid current, including all penalities, interest, and other charges
due with respect to the same.
(b) Registration of Building Contractors: Each builder shall be required
to maintain a registration with the City before performing any type of
construction work. Each contractor shall furnish the building department
with a written notice of contractor's permanent business and residential
address and telephone numbers.
(c) Registration Fees: For a business registration a fee shall be paid in
addition to the other provisions provided herein. The fee for initially
establishing registration data shall be $50.00. The annual renewal fee
for continuing the validity of registration data shall be $25.00.
(d) Registration Renewal: The license may be renewed for the ensuing calendar
year by filing of a new registration and the payment of a renewal fee
as set forth herein. No refund will be paid in the event of the revocation
or surrender of any such certificate of license.
(e) Insurance: Every registrant shall carry contractor's public liability
insurance in not less than the following amounts:
Bodily Injury - $300,000. each occurrence
Property Damage - $100,000. each occurrence
2 -
ORDINANCE NO.889 , PAGE TWO OF ELEVEN 1 11
Section 304 (g) Amend to read:
Whenever public streets, alleys or sidewalks are used for construction
purpose in Fire Zones No. 1 and 2, fees for the use of the space shall
be paid to the Building Official on the following basis:
1. If the time does not exceed three (3) days, the fee will
be $5.00 minimum based on twenty -four (24) hours use per
day per space used.
2. If the time exceeds three (3) days, the fee per day will be
$5.00 minimum plus $1.00 per day.
3. The space for which the fee is paid for construction
purposes shall be for each 50 linear feet occupied.
Section 305 (g) Amend to read:
A reinspection fee may be assessed in accordance with the City of
Euless Schedule of Fees, Table A, Category VI., Ordinance No. 807
when such portion of work for which inspection is called is not
complete or when corrections called for are not made.
This subsection is not to be interpreted as requiring reinspection
fees the first time a job is rejected for failing to comply with
the requirements of this code, but as controlling the practice of
calling for inspections before the job is ready for such inspection
or reinspection.
Reinspection fees may be assessed when the permit card is not
properly posted on the work site, the approved plans are not readily
available to the inspector, for failure to provide access on the
date for which inspection is requested, or for deviating from plans
requiring the approval of the Building Official.
To obtain a reinspection, the applicant shall file an application
therefore in writing upon a form furnished for that purpose and pay
the reinspection fee in accordance with the City of Euless Schedule
of Fees, Table A, Category VI., Ordinance No. 807.
In instances where reinspection fees have been assessed no additional
inspection of the work will be performed until the required fees have
been paid.
Section 503 (d) Sub - paragraph (4) Amend to read:
Fire ratings for Occupancy Separations. In the one -hour occupancy
separation between a Group R -3 and M -1 occupancy, the separation may
be limited to the installation of not less than one -half inch thickness
gypsum board construction on the garage side and a weather - stripped
door will be permitted in lieu of a one -hour fire assembly. Fire
dampers shall not be required-in ducts piercing this separation for
ducts constructed of not less than No. 26 gauge galvanized steel.
ORDINANCE NO. 889 , PAGE THREE OF ELEVEN
- 3 -
Section 513 Amend to read:
Approved numbers or addresses shall be placed on all new and existing
buildings in such a position as to be plainly visible and legible from
the street or road fronting the property. Said numbers shall contrast
with their backbground.
1. Residential occupancies shall have numbers and a minimum of four (4)
inches in height.
2. Multi - family, townhomes, condominums and commercial occupancies
shall have street and /or building numbers a minimum of eight (8)
inches in height. When deemed necessary by the authority having
jurisdiction, the street and /or building numbers may be required
to be of a larger size for immediate and visible identification.
3. If the structure is more than two hundred (200) feet from a public
street, the address shall also appear at the front or main entry to
the property.
4. When deemed necessary by the authority having jurisdiction, the
street or building numbers may be required on more than one side
of the structure or property.
5. Building and /or street numbers shall be located in an area and
lighted in a manner that will make them immediately discernible
as approved by the authority having jurisdiction. Exception:
Neighborhood residential districts containing single family detached
and single family attached (duplex) dwellings.
Chapter 12, Section 1202 of the Uniform Building Code is hereby amended as
follows:
(b) Special Provisions, Group R, Division 1 Occupancies more than
two stories in height or having more than 3000 square feet of
floor area above the first story shall be not less than one -
hour fire - resistive construction throughout except as provided
in Section 1705 (b)2.
Storage or laundry rooms that are within Group R, Division '1
occupancies that are used in common by tenants shall be separated
from the rest of the building by not less than one -hour fire
resistive occupancy separation.
For Group R, Division 1 occupancies with a Group B, Division 1
parking garage in the basement or first floor, see Section 702(a).
For attic space partitions and draft stops, see Section 2516(f)
- 4 -
ORDINANCE NO. 889 , PAGE FOUR OF ELEVEN
(c) An approved automatic fire alarm system shall be installed in
the following occupancies:
1. Multi- family, townhomes and condominum occupancies
containing five or more units joined by common walls
or constructed with a common roof line, regardless of
any area separation and are two or more stories in height.
2. Hotel /motels either two or more stories in height, or
containing 12 or more guest rooms, regardless of any
area separation walls.
3. Educational facilities having an occupant load greater
than 50 persons.
4. Pre - school and /or day care centers having an approved
license for six (6) or more children.
5. Group A, Group B, Group H, and Group I occupancies as
required by NFPA Standard 101 for the maintenance and
notification of the occupants for life safety purposes.
(d) The alarm system shall include provisions for smoke and heat
detection and manual operation as prescribed by the authority
having jurisdiction.
(e) Connection to other systems. A signal system or inter-
communicating system shall not be used for any purpose other
than fire warning unless it meets the requirements of this
article.
(f) Standard for Installation, Inspection and Maintenance.
Installation, inspection and maintenance of the fire alarm
system shall be according to the standards set forth in U.F.C.
Standard No. 10 -2, and applicable to NFPA Standards.
(g) Location of Stations. Stations for operating any manually
operated fire alarm system shall be places immediately adjacent
to the telephone switchboard in the building, if there is a
switchboard, and at such other locations as may be required by
the chief.
(h) Automatic telephone dialing devices to transmit an emergency
alarm shall not be connected to any fire department telephone
number unless approved by the chief.
(i) All control functions necessary to the operation of the fire
alarm system shall be routed through a single control panel
and mounted in an accessible location as approved by the
authority having jurisdiction.
-.5 -
ORDINANCE NO. 889 , PAGE FIVE OF ELEVEN
(j) Where required by the authority having jurisdiction, the fire
alarm systems shall be monitored by an approved central re-
ceiving station meeting NFPA standards.
Section 3203 (c) Add a new section:
Fire retardant Class C roof coverings are required on all multi-
family and townhouse units regardless of the size and height of
the units. Fire retardant Class C roofing materials are defined
as any roofing material whicn meets ASTM E - 108 Fire Test
specifications for roofing and has been tested and approved by
a nationally recognized testing laboratory.
In those cases where it proves necessary to replace all or part
of an ordinary wood shingle roof, and the Class C roofing does
not meet the exposure length of the existing roof, Class C
composition shingles may be overlaid on the wood shingles.
Chapter 33 of the Uniform Building Code is hereby amended to be and read
as follows:
Exit Illumination
Section 3313 (a) General
Except within individual dwelling units, guest rooms and sleeping
rooms, exits shall be illuninated at any time the building is occu-
pied with light having intensity of not less than one foot candle at
floor level.
EXCEPTION: In auditoriums, theaters, concert or opera halls and
similar assembly uses, the illumination at floor level may be re-
duced during performances to not less than 0.2 floor candle.
(b) Power Supply. The power supply for exit illumination shall
normally be provided by the premises wiring system. In the
event of its failure, illumination shall be automatically pro-
vided from an emergency system where the occupancy load of the
occupancy is fifty (50) or more persons. For high -rise buildings,
see Section 1807, and smoke proof enclosures, see Section 3310(g).
Emergency systems shall be supplied from storage batteries in
accordance with the requirements of the Electrical Code.
(c) Windowless or underground areas shall be provided with an
emergency illumination system and approved by the authority
having jurisdiction.
Section 3314 Exit Signs Where Required
(a) Exit signs shall be installed at required exit doorways and
where otherwise necessary to clearly indicate the direction
of egress.
- 6 -
ORDINANCE NO. 889 , PAGE SIX OF ELEVEN
EXCEPTION: Main exterior exit doors which obviously and clearly
are identifiable as exits need not be signed when approved by the
Building Official.
(b) Graphics. The color and design of lettering, arrows and
other symbols on exit signs shall be in high contrast
with their background. Words on the sign shall be in
block letters 6 inches in height with a stroke of not less
than 3/4 inch.
(c) Illumination: Signs shall be internally or externally
illuminated by two electric lamps. When the luminace on
the face of an exit sign is from an external source, it
shall have an intensity of not less than 5.0 feet candles
from either lamp. Internally illuminated signs shall provide
equivalent luminace.
(d) Self luminous type illumination may be approved by the
authority having jurisdiction, when internal or external
illuminated fixtures are not practical or applicable to
the situation.
(e) Power Supply. Power for the exit fixture illumination shall
normally be provided by the premises wiring system. In the
event of its failure, exit sign illumination shall be from
storage batteries or an on -site generator set and the system
be installed in accordance with the electrical code for
emergency lighting provisions.
EXCEPTION: Occupancies in existence at the time of the adoption
of this provision need not comply unless changes, alterations,
or repairs affect their present existence.
For high -rise buildings, see Section 1807.
Section 3315 of the Uniform Building Code is hereby by adding a new
paragraph (i) to read as follows:
(i) Every service aisle, not defined or required as an exitway,
in a commercial retail establishment shall have a clear
aisle width of at least four (4) feet, and shall be main-
tained to at least this width free of obstruction.
Section 3503 Scope of Requirements: Add a new Section
WHEREAS, aircraft exposure Zone "B" has been defined by Article 1,
Section 26 of the Euless Subdivision Rules and Regulations as being
a specific area of Euless having certain significant adverse and
detrimental characteristics due to the operation of aircraft at
the Dallas /Fort Worth Airport; and
7
ORDINANCE NO. 889 , PAGE SEVEN OF ELEVEN
WHEREAS, one of these adverse and detrimental characteristics has
been identified as noise created by aircraft; and
WHEREAS, the levels of noise created by aircraft operating at and
out of the Dallas /Fort Worth Airport are not within the
authority of the City of Euless to regulate; and
WHEREAS, the adverse and detrimental effects of aircraft noise
can be reasonably ameliorated within buildings with the use
of certain construction techniques and materials; and
WHEREAS, the current ordinances and Building Code of the City of
Euless do not address the need for buildings constructed in
such a manner as to attenuate the excess noise levels which
aircraft cause;
For the purpose of this code, every building or structure within
Aircraft Exposure Zone "B" as defined by Article 1, Section 26,
of the Euless Subdivision Rules & Regulations shall be subject
to the following Noise Attenuation Requirements.
Section 3504 Add a new Section
Noise Level Reduction Standards for Certain Uses
The minimum outdoor to indoor noise level reduction for certain
building uses within Zone "B" shall be 25 decibels (A- weighted)
as measured from the center of each room.
BUILDING USE MINIMUM DECIBEL REDUCTION
FROM OUTDOORS TO INDOORS
RESIDENTIAL
Residential within each
unit including transient
lodgings. 25dba
PUBLIC USE
Schools, Hospitals,
Churches, Nursing Homes 25dba
Section 3505 Certification of Plans Prior to Issuance of Building Permit
No building permit for any building or structure designated in
Section 5502 herein, shall be issued unless all plans and
specifications accompanying the application for said permit are
certified by a registered professional architect or engineer of
the State of Texas as meeting the noise level reduction standards
required in Section 5502. The following certification shall appear
on every sheet of the building plans.
1. (Name), a registered professional engineer or architect of the State of
Texas, have examined the plans and specification and do hereby certify
- 8 -
ORDINANCE NO. 889 , PAGE EIGHT OF ELEVEN
that when the structure(s) is constructed in accordance with these
plans and quality workmanship that the structure(s) will provide a
Shell Isolation Rating (S.I.R.) of not less than 25 points.
Chapter 38, Section 3802 of the Uniform Building Code is hereby amended
in the following paragraphs: (c,l; c,3; (d) to be and read as
follows:
(c,l) Group A Occupancies. 1. Night club, discos and restaurants.
An automatic sprinkler system shall be installed in all
occupancies used for drinking or dining, when the total occupancy
area exceeds five thousand (5,000) square feet, regardless of
the area wall separations from other un- separated rooms or area
uses.
(c,3) Assembly areas, exhibition and display rooms. An automatic
sprinkler system shall be installed in all Group A occupancies
which have more than 10,000 square feet of floor area which
can be used for exhibition, assembly or display purpose.
(d) Group B, Division 2 Occupancies. An automatic sprinkler system
shall be installed in all occupancies classed as Group B,
Division 2, where the floor area exceeds twelve thousand (12,000)
square feet on any floor or twenty -four thousand (24,000) square
feet on all floors or in Group B, Division 2 occupancies three
(3) or more stories in height. The area of mezzanines shall be
included in determining the areas where sprinklers are required.
Chapter 38 of the Uniform Building Code, Table 38 -A - Standpipe requirements
No. 2, is hereby amended to read as follows:
2. Occupancies three (3) stories or more, but not less than 150 feet in
height, including apartments, condominiums and townhomes.
Section 3805 of the Uniform Building Code is hereby amended by adding a new
paragraph (f) to read as follows:
(f) Standpipe hose connections for apartments, condominums and town -
homes shall be located on each floor leval and in the areas
of common ingress, in such manner as to provide a hose lay
lay distance no greater than one hundred (100) feet from the
connection to the front doorway of any single unit on that
floor level. Fire department yard connections shall be located
at a distance no greater than ten (10) feet from any firelane
and serving no more than one building.
Standpipe connections shall meet the requirements for material
and construction as outlined in the adopted issue of NFPA
Standard No. 14 for Class I and III dry standpipe systems.
- 9 -
ORDINANCE NO. 889 , PAGE NINE OF ELEVEN
AMENDMENTS TO UNIFORM MECHANICAL CODE
Section 304(a) Amend to read:
(a) The fee for each mechanical permit shall be as set forth in the
City of Euless Schedule of Fees, Table A, Ordinance No. 807.
(b) Registration of Mechanical Contractors: Each contractor shall be
required to maintain a registration with the City before performing
any type of construction work. Each contractor shall furnish
the Building Department with a written notice of contractor's
permanent business and residential address and telephone numbers.
(c) Registration Fees: For a business registration, a fee shall be
paid in addition to the other provisions provided herein. The
fee for initially establishing registration data shall be $50.00.
The annual renewal fee for continuing the validity of registration
data shall be $25.00.
(d) Registration Renewal: The license may be renewed for the ensuing
calendar year by filing of a new registration and the payment of
a renewal fee as set forth herein. No refund will be paid in the
event of the revocation or surrender of any such certificate of
license.
(e) Insurance: Every registrant shall carry contractor's public
liability insurance in not less than the following amounts.
Bodily Injury - $300,000 each occurrence
Property Damage - $100,000 each occurrence
- 10 -
ORDINANCE NO.889 , PAGE TEN OF ELEVEN
All pending litigation and existing violations, both civil and criminal,
whether pending in courts or not, under the building code and amendments there-
fore superseded by this ordinance, shall not be affected by this ordinance until
final disposition by the courts.
III.
SEVERABILITY CLAUSE
That it is hereby declared to be the intention of the City Council that
the sections, paragraphs, sentences, clauses, and phrases of this ordinance
are severable, and if any phrase, clause, sentence, paragraph or section of
this ordinance shall be declared unconstitutional by the valid judgment or
decree of any court of competent jurisdiction, such unconstitutionality shall
not affect any of the remaining phrases, clauses, sentences, paragraphs, and
sections of this ordinance, since the same would have been enacted by the
City Council without the incorporation in this ordinance of any such uncon-
stitutional phrase, clause, sentence, paragraph, or section.
IV.
PENALTY FOR VIOLATION
Any person, firm, or corporation violating any of the terms and provisions
of this ordinance shall be deemed guilty of a misdemeanor and, upon conviction
thereof, shall be fined in an amount not to exceed $1,000.00. Each such
violation shall be deemed a separate offense and shall be punishable as such
hereunder.
V.
EFFECTIVE DATE
This ordinance shall be in full force and effect from and after its
passage and publication as provided by the Euless City Charter and the laws
of the State of Texas.
PRESENTED AND GIVEN FIRST READING at a regular meeting of the Euless City
Council on the 8th day of July 1986 ; by a vote of 4
ayes, 0 nays, and 0 abstentions; GIVEN SECOND READING
AND APPROVED at a regular meeting of the Euless City Council on the 26th
day of August , 1986 , by a vote of 5 ayes, 0
nays, and
ATTEST:
0 abstentions.
APPROVED:
APPROVED AS 'CO
CITY SEC ETARY
ORDINANCE NO. 889 , PAGE ELEVEN OF ELEVEN
MAYOR
at4'1
CITY ATTORNEY